| Technical Specifications | ||
| Environmental requirements | Operating temperature | -40°C to +65°C |
| Transportation temperature | -40°C to +70°C | |
| Storage temperature | -40°C to +70°C | |
| Operating humidity | 5%–95% RH (non-condensing) | |
| Storage humidity | 5%–95% RH (non-condensing) | |
| Altitude | 0-4000 m | |
| When the altitude ranges from 2000 m to 4000 m, the operating temperature decreases by 1°C for each additional 200 m. | ||
| AC input | Input system | 220/380 V AC, three-phase, four-wire compatible with 220 V AC single-phase |
| Input frequency | 45-66 Hz (rated frequency: 50 Hz or 60 Hz) | |
| Power factor (PF) | ≥ 0.99 (rated input, with loads) | |
| Total harmonic distortion (THD) | ≤ 10% | |
| Vin = 208 V AC, 220 V AC, 230 V AC, or 240 V AC, where | ||
| 50%–100% load percentage | ||
| DC output | Output voltage range | -42 V DC to -58 V DC |
| Default output voltage | -53.5 V DC | |
| Max. output power | 12000 W (supports N+1 backup and keeps long-term operating current output within 150 A) | |
| Regulated voltage precision | ≤ ±1% (The output voltage is within 53.5 V DC ±0.1 under 50% loads.) | |
| Peak-to-peak noise voltage | ≤ 200 mV (rated input voltage and load) | |
| Noise weighting | ≤ 2 mV (300–3400 Hz, input power ≤ 264 V AC) | |
| Unbalance of load sharing | ≤ ±5% (with 20% to 100% loads) | |
| AC input protection | AC input overvoltage protection threshold | ≥ 300 V AC |
| AC input overvoltage recovery threshold | 290–300 V AC | |
| AC input undervoltage protection threshold | ≤ 80 V AC | |
| AC input undervoltage recovery threshold | 80–90 V AC | |
| DC output protection | DC output overvoltage protection threshold | -58.5 V DC to -60.5 V DC |
| Structure | Dimensions (H x W x D) | 220.3 mm x 482 mm x 330.6 mm |
| Weight | ≤ 20 kg (without rectifiers) | |
| Protection level | IP20 | |
| Installation mode | Equipped with mounting ears to adapt to 19-inch cabinets | |
| Cable routing | Routed in and out from the top | |
| Maintenance mode | Maintained from the front | |
| Heat dissipation mode | Natural heat dissipation | |
| PDU specification | ||
| Input system | 220/380 V AC, three-phase, four-wire compatible with 220 V AC single-phase | |
| AC input circuit breaker | One 3-pole 32 A | |
| DC power distribution | LLVD circuit breakers: three 1-pole 32 A and six 1-pole 16 A BLVD circuit breakers: three 1-pole 16 A, three 1-pole 10 A, and one 1-pole 6 A |
|
| Battery circuit breakers | Two 1-pole 125 A | |
| Configurations | ||
| Applicable environment | Indoor Class B | |
| Subrack | 3 U power distribution space 1 U monitoring unit 1 U rectifier space |
|
| Power distribution unit (PDU) | AC power distribution: AC input circuit breaker DC power distribution: battery low voltage disconnection (BLVD) route, load low voltage disconnection (LLVD) route, and battery route |
|
| Rectifier | A maximum of four R4850N2s or R4850G2s | |
| Site monitoring module (SMU) | SMU02B | |
| User interface module (UIM) | UIM02C | |
| Surge protective device (SPD) | DC surge protection: 10 kA (8/20 µs) in differential mode, 20 kA (8/20 µs) in common mode | |