| Technical Specifications |
| Environment conditions |
Operating temperature |
–40°C to +65°C (When the ambient temperature is between –33°C and +55°C, the power system works properly. When the ambient temperature is greater than 55°C and less than or equal to 65°C, the output power is linearly derated to 80%. When the ambient temperature is –40°C, the power system can start properly after AC power is applied.) |
| Transportation temperature |
–40°C to +70°C |
| Storage temperature |
–40°C to +70°C |
| Operating humidity |
5%–95% RH (non-condensing) |
| Storage humidity |
5%–95% RH (non-condensing) |
| Altitude |
0–4000 m |
| When the altitude ranges from 2000 m to 4000 m, the operating temperature decreases by 1°C for each additional 200 m. |
| Noise |
System audible noise: ≤ 60 dBA at 25°C, ≤ 72 dBA at 40°C; meets class 3.1 requirements of ETSI 300753. |
| Others |
There is no conductive dust, corrosive gas, or explosion hazard. |
| Dust, corrosive substances, pests, molds, and other indicators should be controlled in accordance with class 3.1 requirements in ETSI EN 300 019-1-3 (V2.3.2 or a later version). |
| AC input |
Input frequency |
45–66 Hz; rated frequency: 50 Hz/60 Hz |
| Power factor |
≥ 0.99 (rated input voltage, 50%–100% load) |
| DC output |
Output voltage |
–53.5 V DC |
| Maximum output power |
ETP48400-C3B2: 18 kW |
| Regulated voltage precision |
≤ ±1% |
| Peak-to-peak noise voltage |
≤ 200 mV (0–20 MHz) |
| Psophometrically weighted noise voltage |
≤ 2 mV |
| Unbalance of load sharing |
≤ ±5% (50%–100% load) |
| AC input protection |
AC input overvoltage protection threshold |
≥ 300 V AC |
| AC input overvoltage recovery threshold |
290–300 V AC |
| AC input undervoltage protection threshold |
≤ 80 V AC |
| AC input undervoltage recovery threshold |
80–90 V AC |
| DC output protection |
DC output overvoltage protection threshold |
–56 V DC to –60.5 V DC (default: 59.5 V DC) |
| Structure |
Dimensions (H x W x D) |
130 mm x 482 mm x 330 mm |
| Weight |
≤ 20 kg (excluding rectifiers) |
| IP rating |
IP20 |
| Installation mode |
Installed in a 19-inch rack |
| Cabling mode |
Routed in and out from the front |
| Maintenance mode |
Maintained from the front |
| Heat dissipation mode |
Free cooling |
| System Specifications |
| AC input system |
120/240 V AC dual-live wire |
| DC power distribution |
LLVD: two 125 A and three 63 A circuit breakers |
| BLVD: two 63 A, two 32 A, and two 16 A circuit breakers |
| Surge protection |
AC surge protection: nominal surge discharge current: 30 kA (8/20 µs), five times respectively in the positive and negative directions |
| DC surge protection: 10 kA (8/20 µs) in differential mode, 20 kA (8/20 µs) in common mode |