5U height composed by 9xRectifier 1xSMU02C 1xUIM05B1
Maximum power capacity: 36 kW with three-phase four-wire or three–live wire input
Maximum power capacity: 28 kW with dual–live wire or single-phase input
LLVD: 2 x 125 A/1P, 3 x 63 A/1P
BLVD: 2 x 63 A/1P, 2 x 32 A/1P, 2 x 16 A/1P
Battery route: 6 x 125 A/1P
(Optional) Communications Expansion Module: NIM01C3 or CIM02C
(Optional) Power Distribution Unit: DCDB48-200-16B, iDCDB200B or iDCDU100D1
The ETP48600-C5A2 is an embedded power system that converts AC power into DC power. It supplies –48 V and –57 V constant voltage to load equipment. Its maximum power capacity is 36 kW with three-phase four-wire or three–live wire input, and 28 kW with dual–live wire or single-phase input. It can be used at newly built sites and capacity expansion and reconstruction scenarios of existing sites.
Technical Specifications | ||
Environment specifications | Operating temperature | –40°C to +65°C |
(When the ambient temperature ranges from –33°C to +55°C, this product works properly. When the ambient temperature ranges from 55°C to 65°C, the output power linearly derates by 20%. When the ambient temperature is –40°C, this product starts properly after the AC power supply is connected. There is no requirement for the output voltage waveform at startup.) | ||
Transportation temperature | –40°C to +70°C | |
Storage temperature | –40°C to +70°C | |
Operating humidity | 5%–95% RH (non-condensing) | |
Transportation humidity | 5%–95% RH (non-condensing) | |
Storage humidity | 5%–95% RH (non-condensing) | |
Altitude | 0–4000 m | |
(When the altitude ranges from 2000 m to 4000 m, the operating temperature decreases by 1°C for each additional 200 m.) | ||
Others | There is no conductive dust, corrosive gas, or explosion hazard. | |
Dust, corrosive substances, pests, molds, and other indicators should be controlled in accordance with Class 3.1 requirements in ETSI EN 300 019-1-3 (V2.3.2 or later). | ||
AC input | Input system | 220/380 V AC three-phase four-wire |
220 V AC three–live wire | ||
110 V AC dual–live wire, compatible with 220 V AC single-phase | ||
Input frequency | 45–66 Hz; rated value: 50 Hz/60 Hz | |
Power factor (PF) | ≥ 0.99 (rated input voltage, 50%–100% load) | |
DC output | Output voltage range | 48 V mode: –42 V DC to –58 V DC (–53.5 V DC by default) |
57 V mode: –48 V DC to –57 V DC (–57 V DC by default) | ||
Maximum output power | 36 kW (three-phase four-wire AC input) | |
36 kW (three–live wire AC input) | ||
28 kW (single-phase or dual–live wire AC input) | ||
Voltage detection precision | ±0.5% | |
Current detection precision | ±1%(load current:200A~450A) | |
±2A(load current<200A) | ||
Regulated voltage precision | ≤ ±1% | |
Peak-to-peak noise voltage | ≤ 200 mV (0–20 MHz) | |
Psophometrically weighted noise voltage | ≤ 2 mV (meets this standard at rated output voltage points of 53.5 V and 57 V) | |
Current sharing imbalance | ≤ ±5% (20%–100% load) | |
AC input protection | AC input overvoltage protection threshold | ≥ 300 V AC |
AC input overvoltage recovery threshold | 290–300 V AC | |
AC input undervoltage protection threshold | ≤ 80 V AC | |
AC input undervoltage recovery threshold | 80–90 V AC | |
DC output protection | DC output overvoltage protection threshold | Range: –58.5 V DC to –60.5 V DC |
Structure | Power system (H x W x D) | 219.5 mm x 482.6 mm x 330 mm |
Weight | ≤ 25 kg (excluding rectifiers) | |
IP rating | IP20 | |
Installation mode | Installed in a 19-inch rack | |
Cabling | Routed in and out from the front | |
Maintenance mode | Maintained from the front | |
Cooling mode | Free cooling | |
System configuration | ||
AC input system | 220/380 V AC three-phase four-wire | |
220 V AC three–live wire | ||
110 V AC dual–live wire, compatible with 220 V AC single-phase | ||
(Optional) AC power distribution | AC output module (AOU03-16C): 3 x 16 A circuit breakers | |
Intelligent AC output module (iAOU03-16B): 2 x 16 A circuit breakers
NOTE: |
||
DC power distribution | LLVD: 2 x 125 A/1P, 3 x 63 A/1P | |
BLVD: 2 x 63 A/1P, 2 x 32 A/1P, 2 x 16 A/1P | ||
Battery route: 6 x 125 A/1P | ||
Surge protection | No surge protection is provided for the AC input. An upstream ACDB with the surge protection function is required. | |
DC surge protection: 10 kA (8/20 µs) in differential mode, 20 kA (8/20 µs) in common mode |
As a global leading professional Huawei network hardware and solution provider, we have delivered Huawei, ZTE, Nokia, CISCO, Fiberhome, etc, equipment to 500+ customer groups in 90+ countries over the past 10 years. Know more
Strict 3-Level Quality Control procedure: 1st-Level inspection; 2nd-Level In-stock test; 3rd-Level 24-hour pre-delivery test to guarantee premium quality. Know more
What we offer to our customers is value rather than price. We enable customers to enjoy the benefit of our reliable delivery products and generate more value to the greatest extent. Know more
We provide customers with personalized and professional tech support by remote diagnosis, fault-location and troubleshooting. "We are here to help you instantly when you need it."
We continuously offer flexible payment methods such as Wire Transfer, Paypal, L/C, Western Union and Alipay, to help customer enjoy a more convenient shopping experience. Know more
We provide extensive document resources to guide our customers to targetly solve the problem they may meet. Know more
Our products come with 1-year warranty. Customers can ask for a repair, replacement or refund for a major product failure. Know more
We won't stop to develop rapid and cost effective shipping options, providing the excellent experience to our global customers. Know more
We offer not only network products but also network proposal, mainstream and cost-effective solution to assist customers eliminate the concerns.
ETP48600-C5A2 600A power converter with 9xRectifier 1xSMU02C 1xUIM05B1
(0 reviews) | 0
Reviews
There are no reviews yet.