ETP48600-C5A6

ETP48600-C5A6 600A power converter with 9xR4875G5 1xSMU02C 1xUIM05B1

inquire lead time

13 People watching this product now!
Category:

Description

5U height composed by 9xR4875G5 1xSMU02C 1xUIM05B1

LLVD: 2 x 125 A/1P, 3 x 63 A/1P

BLVD: 2 x 63 A/1P, 2 x 32 A/1P, 2 x 16 A/1P

Battery route: 6×125A/1P

Supports AIU03-63C, AIU03-63D, AIU02-125B or AIU03-100C as AC input module

Supports AOU03-16C or iAOU03-16B as AC output module

(Optional) Communications Expansion Module: NIM01C3 or CIM02C

(Optional) Power Distribution Unit: DCDB48-200-16B, iDCDB200B or iDCDU100D1

(Optional) Lithium Battery: ESM-48100B1 or ESM-48150B1

 

The ETP48600-C5A6 is an embedded power systems that convert AC power into DC power, and supplies –48 V or –57 V constant voltage to load equipment. The maximum capacity of the power systems is 36 kW. It applies to newly built sites and capacity expansion and reconstruction scenarios of existing sites.

Tech Specs
Technical Specifications
Environmental conditions Operating temperature –40°C to +65°C
(When the ambient temperature ranges from –33°C to +55°C, this product works properly. When the ambient temperature ranges from 55°C to 65°C, the output power linearly derates by 20%. When the ambient temperature is –40°C, this product starts properly after the AC power supply is connected. There is no requirement for the output voltage waveform at startup.)
Transportation temperature –40°C to +70°C
Storage temperature –40°C to +70°C
Operating humidity 5%–95% RH (non-condensing)
Transportation humidity 5%–95% RH (non-condensing)
Storage humidity 5%–95% RH (non-condensing)
Altitude 0–4000 m
(When the altitude ranges from 2000 m to 4000 m, high temperature derating applies and the operating temperature decreases by 1°C for each additional 200 m.)
Others There is no conductive dust, corrosive gas, or explosion hazard.
Dust, corrosive substances, pests, molds, and other indicators should be controlled in accordance with class 3.1 requirements in ETSI EN 300 019-1-3 (V2.3.2 or a later version).
AC input Input frequency 45–66 Hz; rated value: 50 Hz/60 Hz
Power factor (PF) ≥ 0.99 (rated input voltage, 50%–100% load)
DC output Output voltage range 48 V mode: –42 V DC to –58 V DC (–53.5 V DC by default)
57 V mode: –48 V DC to –57 V DC (–57 V DC by default)
Regulated voltage precision ≤ ±1%
Peak-to-peak noise voltage ≤ 200 mV (0–20 MHz)
Psophometrically weighted noise voltage ≤ 2 mV (meets this standard at rated output voltage points of 53.5 V and 57 V)
Current sharing imbalance ≤ ±5% (20%–100% load)
AC input protection AC input overvoltage protection threshold ≥ 300 V AC
AC input overvoltage recovery threshold 290–300 V AC
AC input undervoltage protection threshold ≤ 80 V AC
AC input undervoltage recovery threshold 80–90 V AC
DC output protection DC output overvoltage protection threshold Range: –58.5 V DC to –60.5 V DC
Structure Power system (H x W x D) 219.5 mm x 482.6 mm x 330 mm
Weight ≤ 25 kg (excluding rectifiers)
IP rating IP20
Installation mode Installed in a 19-inch rack
Cabling Routed in and out from the front
Maintenance mode Maintained from the front
Cooling mode Natural cooling
System configuration
Number of AC inputs Supports two inputs (manual switching, mechanical interlock). The corresponding rectifiers are PSU1 to PSU9.
AC input module AIU03-63C (02312KUQ)
Module Specifications: 63 A/3P + N terminal
Input System: 220/380 V AC three-phase four-wire, compatible with 220 V AC single-phase
Maximum Capacity: Three-phase 24 kW; Single-phase 18 kW
AIU03-63D(02312MMH-002)
Module Specifications: 63 A/4P
Input System: 220/380 V AC three-phase four-wire
Maximum Capacity: 24 kW, supports two inputs and mechanical interlock.
AIU02-125B(02312MKG)
Module Specifications: 125 A/2P
Input System: 110 V AC dual–live wire
Maximum Capacity: 18 kW
AIU03-100C(02312MUD)
Module Specifications: 100 A/3P + N
Input System: 220/380 V AC three-phase four-wire
Maximum Capacity: 36 kW, supports two inputs and mechanical interlock.
AC output module AOU03-16C (02312WSX)
3 x 16 A/1P circuit breaker
iAOU03-16B (02312WSX-001)
Two 1-pole 16 A circuit breakers and one -48 V AC meter
DC output route (optional) Configuration example:
LLVD: 2 x 125 A/1P, 3 x 63 A/1P
BLVD: 2 x 63 A/1P, 2 x 32 A/1P, 2 x 16 A/1P
Battery route 6x125A/1P
Surge protection AC surge protection: nominal surge discharge current: 30 kA (8/20 µs), five times respectively in the positive and negative directions
DC surge protection: 10 kA (8/20 µs) in differential mode, 20 kA (8/20 µs) in common mode
Reviews (0)

Reviews

There are no reviews yet.

Be the first to review “ETP48600-C5A6”

Your email address will not be published. Required fields are marked *

You have to be logged in to be able to add photos to your review.

Why Thunder-link.com

10 Years Experience

As a global leading professional Huawei network hardware and solution provider, we have delivered Huawei, ZTE, Nokia, CISCO, Fiberhome, etc, equipment to 500+ customer groups in 90+ countries over the past 10 years. Know more

Premium Quality Guaranteed

Strict 3-Level Quality Control procedure: 1st-Level inspection; 2nd-Level In-stock test; 3rd-Level 24 hour pre-delivery test to guarantee premium quality. Know more

Value over price

What we offer to our customers is value rather than price. We make customers enjoy the benefit of our reliable delivery products and generate more value to the greatest extent. Know more

Tailored Technical Support

We provide customers personalized and professional tech support by remote diagnosis, fault-location and troubleshooting. "We are here to help you instantly when you need it."

Flexible Payment

We continuously offer flexible payment methods such as Wire Transfer, Paypal, L/C, Western Union and Alipay, to help customer enjoy a more convenient shopping experience. Know more

Official Document Resource

We provide official and extensive document resources to guide our customers to targetly solve the problem they may meet. Know more

1 Year Warranty Guaranteed

Our products come with 1 year warranty. Customers can ask for a repair, replacement or refund for a major product failure. Know more

Fast Global Shipping

We won't stop to develop rapid and cost effective shipping options, provide the excellent experience for our global customers. Know more

One Stop Solution

We provide not only network products but also network proposal, mainstream and cost efficient solution to assist customers eliminate the concerns.