| Technical Specifications |
| Environmental conditions |
Operating temperature |
–40°C to +65°C |
| (When the ambient temperature ranges from –33°C to +55°C, this product works properly. When the ambient temperature ranges from 55°C to 65°C, the output power linearly derates by 20%. When the ambient temperature is –40°C, this product starts properly after the AC power supply is connected. There is no requirement for the output voltage waveform at startup.) |
| Transportation temperature |
–40°C to +70°C |
| Storage temperature |
–40°C to +70°C |
| Operating humidity |
5%–95% RH (non-condensing) |
| Transportation humidity |
5%–95% RH (non-condensing) |
| Storage humidity |
5%–95% RH (non-condensing) |
| Altitude |
0–4000 m |
| (When the altitude ranges from 2000 m to 4000 m, high temperature derating applies and the operating temperature decreases by 1°C for each additional 200 m.) |
| Others |
There is no conductive dust, corrosive gas, or explosion hazard. |
| Dust, corrosive substances, pests, molds, and other indicators should be controlled in accordance with class 3.1 requirements in ETSI EN 300 019-1-3 (V2.3.2 or a later version). |
| AC input |
Input frequency |
45–66 Hz; rated value: 50 Hz/60 Hz |
| Power factor (PF) |
≥ 0.99 (rated input voltage, 50%–100% load) |
| DC output |
Output voltage range |
48 V mode: –42 V DC to –58 V DC (–53.5 V DC by default) |
| 57 V mode: –48 V DC to –57 V DC (–57 V DC by default) |
| Regulated voltage precision |
≤ ±1% |
| Peak-to-peak noise voltage |
≤ 200 mV (0–20 MHz) |
| Psophometrically weighted noise voltage |
≤ 2 mV (meets this standard at rated output voltage points of 53.5 V and 57 V) |
| Current sharing imbalance |
≤ ±5% (20%–100% load) |
| AC input protection |
AC input overvoltage protection threshold |
≥ 300 V AC |
| AC input overvoltage recovery threshold |
290–300 V AC |
| AC input undervoltage protection threshold |
≤ 80 V AC |
| AC input undervoltage recovery threshold |
80–90 V AC |
| DC output protection |
DC output overvoltage protection threshold |
Range: –58.5 V DC to –60.5 V DC |
| Structure |
Power system (H x W x D) |
219.5 mm x 482.6 mm x 330 mm |
| Weight |
≤ 25 kg (excluding rectifiers) |
| IP rating |
IP20 |
| Installation mode |
Installed in a 19-inch rack |
| Cabling |
Routed in and out from the front |
| Maintenance mode |
Maintained from the front |
| Cooling mode |
Natural cooling |
| System configuration |
| Number of AC inputs |
Two inputs can supply power at the same time
AC input 1 corresponds to PSU1 to PSU6
AC input 2 corresponds to PSU7 to PSU9 |
| AC input module |
AIU03-63C (02312KUQ)
Module Specifications: 63 A/3P + N terminal
Input System: 220/380 V AC three-phase four-wire, compatible with 220 V AC single-phase
Maximum Capacity: Three-phase 24 kW; Single-phase 18 kW |
AIU03-63D(02312MMH-002)
Module Specifications: 63 A/4P
Input System: 220/380 V AC three-phase four-wire
Maximum Capacity: 24 kW, supports two inputs and mechanical interlock. |
AIU02-125B(02312MKG)
Module Specifications: 125 A/2P
Input System: 110 V AC dual–live wire
Maximum Capacity: 18 kW |
AIU03-100C(02312MUD)
Module Specifications: 100 A/3P + N
Input System: 220/380 V AC three-phase four-wire
Maximum Capacity: 36 kW, supports two inputs and mechanical interlock. |
| AC output module |
AOU03-16C (02312WSX)
3 x 16 A/1P circuit breaker |
iAOU03-16B (02312WSX-001)
Two 1-pole 16 A circuit breakers and one -48 V AC meter |
| DC output route (optional) |
Configuration example: |
| LLVD: 2 x 125 A/1P, 3 x 63 A/1P |
| BLVD: 2 x 63 A/1P, 2 x 32 A/1P, 2 x 16 A/1P |
| Battery route |
6x125A/1P |
| Surge protection |
AC surge protection: nominal surge discharge current: 30 kA (8/20 µs), five times respectively in the positive and negative directions |
| DC surge protection: 10 kA (8/20 µs) in differential mode, 20 kA (8/20 µs) in common mode |