TP48200A-D14A1 Outdoor Site Power Cabinet
in stock inquire lead time
Cabinet height: 1400 mm
Heat dissipation type: in forced ventilation mode
Rated output current: 200A
Rated output voltage: 48V
Supports PMU Panel, including UIM02A user interface module and PMU02C1 monitoring unit
PMU02C1 supports WebUI
UIM02A provides sensor ports, Boolean value input ports, and dry contact output ports.
Supports 1 group 100Ah VRLA batteries
The TP48200A-D14A1 is an outdoor cabinet-type power system and supplies power to the -48 V DC telecom equipment. The TP48200A-D14A1 uses 50 A rectifiers and outputs a maximum of 200 A current.
Cabinet Description | ||
Structure | Dimensions (H x W x D) | Cabinet (without base): 1400 mm x 650 mm x 700 mm (55.11 in. x 25.59 in. x 27.56 in.).
Base: 100 mm x 650 mm x 700 mm (3.94 in. x 25.59 in. x 27.56 in.) |
Weight | 200 kg (without storage batteries and rectifiers) | |
Space for customer | More than 10U | |
Protection level | Equipment compartment is IP55
Battery compartment is IP23 |
|
Installation and carrying | Mounted on concrete pad and carried by using a hoist | |
Maintenance | From the front, supporting module-level replacement. | |
Cabling | Bottom inlet and bottom outlet | |
Heat dissipation mode | Direct ventilation | |
Heat dissipation capability | More than 1500 W | |
Technical Specifications | ||
Environmental conditions | Operating temperature | –10ºC to +50ºC (+14ºF to +122ºF) |
Storage temperature | –40°C to +70°C (–40°F to +158°F) | |
Transportation temperature | –40°C to +70°C (–40°F to +158°F) | |
Operating humidity | 5%–95% RH (non-condensing) | |
Storage humidity | 5%–95% RH (non-condensing) | |
Altitude |
0–4000 m (013123.2 ft) When the altitude ranges from 3000 m (9842.4 ft) to 4000 m (13123.2 ft), the operating temperature is derated by 1ºC (1.8ºF) for each additional 100 m (328.08 ft). |
|
AC input | Input mode | Single phase three wire (L, N, and PE) |
Input voltage | 90–290 V AC (rated voltage: 220 V AC) | |
Input frequency | 40–65 Hz (rated frequency: 50/60 Hz) | |
Power factor | ≥ 0.99 (rated load) | |
DC output | Output voltage range | –42 V DC to –58V DC |
Default output voltage | –53.5 V DC | |
Maximum output power | Number of rectifiers multiplied by the output power of a single rectifier | |
Regulated voltage precision | ≤ 1% | |
Peak-to-peak noise voltage | ≤ 200 mV (0–20 MHz) | |
Others | No damage is caused if a storage battery is connected reversely. | |
AC input protection | AC input overvoltage protection threshold | Overvoltage protection is performed when the single-phase AC input voltage exceeds the AC input overvoltage protection threshold (300 V AC by default). |
AC input overvoltage recovery threshold | When the voltage is restored to 290 V AC, the output resumes. | |
AC input undervoltage protection threshold | Undervoltage protection is performed when the single-phase AC input voltage is below the AC input undervoltage protection threshold (85 V AC by default). | |
AC input undervoltage recovery threshold | When the voltage is restored to 90 V AC, the output resumes. | |
DC output protection | DC output overvoltage protection threshold | 58.5–60.5 V DC |
Others | AC surge protection | Level-B surge protection
Standard surge discharge current: 30 kA, 8/20 µs Maximum surge discharge current: 60 kA |
Safety and regulatory design | IEC60950-1, IEC 60950-22 | |
MTBF | 100,000 hours | |
Power distribution specifications | ||
AC power distribution | Main AC input | One 100 A two-pole MCB; |
DC power distribution | Load shutdown | BLVD: 10 A MCB x 2; 16 A MCB x 3
LLVD: 20 A MCB x 8; 63 A MCB x 1 |
Battery branch | 100 A MCB x 1 | |
Configuration | ||
The TP48200A-D14A1 power system mainly consists of the cabinet, temperature control unit (TCU), rectifier, power distribution unit (PDU), and monitoring unit. | ||
Item | Composition | AC input mode |
TP48200A-D14A1 | PMU02C1
UIM02A R4850G1 PDU |
Single phase three wire |
As a global leading professional Huawei network hardware and solution provider, we have delivered Huawei, ZTE, Nokia, CISCO, Fiberhome, etc, equipment to 500+ customer groups in 90+ countries over the past 15 years. Know more
Strict 3-Level Quality Control procedure: 1st-Level inspection; 2nd-Level In-stock test; 3rd-Level 24-hour pre-delivery test to guarantee premium quality. Know more
What we offer to our customers is value rather than price. We enable customers to enjoy the benefit of our reliable delivery products and generate more value to the greatest extent. Know more
We provide customers with personalized and professional tech support by remote diagnosis, fault-location and troubleshooting. "We are here to help you instantly when you need it."
We continuously offer flexible payment methods such as Wire Transfer, Paypal, L/C, Western Union and Alipay, to help customer enjoy a more convenient shopping experience. Know more
We provide extensive document resources to guide our customers to targetly solve the problem they may meet. Know more
Our products come with 1-year warranty. Customers can ask for a repair, replacement or refund for a major product failure. Know more
We won't stop to develop rapid and cost effective shipping options, providing the excellent experience to our global customers. Know more
We offer not only network products but also network proposal, mainstream and cost-effective solution to assist customers eliminate the concerns.
TP48200A-D14A1 Outdoor Site Power Cabinet
|