| Cabinet Description |
| Structure |
Dimensions (H x W x D) |
Cabinet (without base): 1400 mm x 650 mm x 700 mm (55.11 in. x 25.59 in. x 27.56 in.).
Base: 100 mm x 650 mm x 700 mm (3.94 in. x 25.59 in. x 27.56 in.) |
| Weight |
200 kg (without storage batteries and rectifiers) |
| Space for customer |
More than 10U |
| Protection level |
Equipment compartment is IP55
Battery compartment is IP23 |
| Installation and carrying |
Mounted on concrete pad and carried by using a hoist |
| Maintenance |
From the front, supporting module-level replacement. |
| Cabling |
Bottom inlet and bottom outlet |
| Heat dissipation mode |
Direct ventilation |
| Heat dissipation capability |
More than 1500 W |
| Technical Specifications |
| Environmental conditions |
Operating temperature |
–10ºC to +50ºC (+14ºF to +122ºF) |
| Storage temperature |
–40°C to +70°C (–40°F to +158°F) |
| Transportation temperature |
–40°C to +70°C (–40°F to +158°F) |
| Operating humidity |
5%–95% RH (non-condensing) |
| Storage humidity |
5%–95% RH (non-condensing) |
| Altitude |
0–4000 m (013123.2 ft)
When the altitude ranges from 3000 m (9842.4 ft) to 4000 m (13123.2 ft), the operating temperature is derated by 1ºC (1.8ºF) for each additional 100 m (328.08 ft).
|
| AC input |
Input mode |
Single phase three wire (L, N, and PE) |
| Input voltage |
90–290 V AC (rated voltage: 220 V AC) |
| Input frequency |
40–65 Hz (rated frequency: 50/60 Hz) |
| Power factor |
≥ 0.99 (rated load) |
| DC output |
Output voltage range |
–42 V DC to –58V DC |
| Default output voltage |
–53.5 V DC |
| Maximum output power |
Number of rectifiers multiplied by the output power of a single rectifier |
| Regulated voltage precision |
≤ 1% |
| Peak-to-peak noise voltage |
≤ 200 mV (0–20 MHz) |
| Others |
No damage is caused if a storage battery is connected reversely. |
| AC input protection |
AC input overvoltage protection threshold |
Overvoltage protection is performed when the single-phase AC input voltage exceeds the AC input overvoltage protection threshold (300 V AC by default). |
| AC input overvoltage recovery threshold |
When the voltage is restored to 290 V AC, the output resumes. |
| AC input undervoltage protection threshold |
Undervoltage protection is performed when the single-phase AC input voltage is below the AC input undervoltage protection threshold (85 V AC by default). |
| AC input undervoltage recovery threshold |
When the voltage is restored to 90 V AC, the output resumes. |
| DC output protection |
DC output overvoltage protection threshold |
58.5–60.5 V DC |
| Others |
AC surge protection |
Level-B surge protection
Standard surge discharge current: 30 kA, 8/20 µs
Maximum surge discharge current: 60 kA |
| Safety and regulatory design |
IEC60950-1, IEC 60950-22 |
| MTBF |
100,000 hours |
| Power distribution specifications |
| AC power distribution |
Main AC input |
One 100 A two-pole MCB; |
| DC power distribution |
Load shutdown |
BLVD: 10 A MCB x 2; 16 A MCB x 3
LLVD: 20 A MCB x 8; 63 A MCB x 1 |
| Battery branch |
100 A MCB x 1 |
| Configuration |
| The TP48200A-D14A1 power system mainly consists of the cabinet, temperature control unit (TCU), rectifier, power distribution unit (PDU), and monitoring unit. |
| Item |
Composition |
AC input mode |
| TP48200A-D14A1 |
PMU02C1
UIM02A
R4850G1
PDU |
Single phase three wire |