Cabinet Specifications
|
| Dimensions (H x W x D) |
480 mm x 442 mm x 360 mm |
| Weight |
≤ 30 kg (excluding rectifiers) |
| Protection level |
IP20 |
| Installation mode |
Floor mounted, wall mounted, battery stacked, or 19- or 21-inch standard rack mounted |
| Maintenance mode |
Maintained from the front and located against a wall (at least 100 mm away from the wall) |
| Cabling |
Routed in and out from the top |
| Heat dissipation |
Cools as the ambient temperature drops |
| Configuration |
| Rectifier |
A maximum of six R4850G2s or R4830G2s |
| Maximum output current |
300 A |
| Power distribution unit (PDU) |
AC PDU: AC input circuit breaker
DC PDU: BLVD route, LLVD route, battery route |
| Site monitoring unit (SMU) |
SMU06C |
| surge protection device (SPD) |
nominal surge discharge current: 20 kA (8/20 µs); maximum surge discharge current: 40 kA (8/20 µs) |
| PDU specifications |
| AC power distribution |
AC input circuit breaker |
One 3-pole 63 A circuit breaker |
| AC output circuit breaker |
One 2-pole 16 A circuit breaker (reserved) |
| Rectifier AC input circuit breaker |
Six 1-pole 63 A circuit breakers (reserved) |
| DC power distribution |
BLVD route |
One 1-pole 63 A circuit breaker, one 1-pole 32 A circuit breaker, and two 1-pole 16 A circuit breakers |
| LLVD route |
One 1-pole 100 A circuit breaker and two 1-pole 80 A circuit breakers |
| Battery route |
Two 1-pole 160 A fuse |
| Electrical Specifications |
| AC input |
Input system |
220/380 V AC three-phase, four-wire input system (compatible with 220 V AC single-phase input systems) |
| Input voltage |
85 V AC–300 V AC |
| Input frequency |
Range: 45-66 Hz; nominal frequency: 50/60 Hz |
| Power factor |
≥ 0.99 (Rated input and full load) |
| Total harmonic distortion (THD) |
≤ 5% (Vin = 208 V AC, 220 V AC, 230 V AC, 50%-100% load) |
| DC output |
Output voltage range |
-42 V DC to -58 V DC |
| Default output voltage |
–53.5 V DC |
| Output power |
Maximum output power = Output power of a single rectifier x Number of rectifiers |
| Regulated voltage precision |
≤ ±1% |
| Ripple and noise |
≤ 200 mVp-p |
| Noise weighting |
≤ 2 mV |
| Imbalance of load sharing |
< ±5% (20%-100% loaded) |
| AC input protection |
AC input overvoltage protection threshold |
300 V AC |
| AC input overvoltage recovery threshold |
When the voltage is restored to 290 V AC, the output resumes. |
| AC input undervoltage protection threshold |
< 85 V AC |
| AC input undervoltage recovery threshold |
When the voltage is restored to 90 V AC, the output resumes. |
| DC output protection |
DC output overvoltage protection threshold |
Range: 58.5-60.5 V DC
1. If an overvoltage occurs due to an internal fault in a rectifier, the rectifier locks out.
2. If the external voltage is higher than 63 V for more than 500 ms, the rectifier locks out. |
| AC surge protection |
Level-C surge protection, nominal lightning strike discharge current: 20 kA (8/20 µs). The maximum lightning strike discharge current is 40 kA (8/20 µs). |
| DC surge protection |
Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs) |
| Safety and regulatory design |
Complies with the IEC/EN60950-1. |
| Mean time between failures (MTBF) |
200,000 hours (at 25°C) |