Cabinet Specifications
|
| Cabinet dimensions (H x W x D) |
2000 mm x 600 mm x 600 mm |
| Weight |
≤ 126 kg (excluding rectifiers and batteries) |
| Protection level |
IP20 |
| Installation mode |
Installed on a concrete floor or an ESD floor |
| Maintenance mode |
Maintained from the front and installed on a wall with a clearance of at least 100 mm |
| Cabling |
Routed in and out from the top of the cabinet |
| Configuration |
| AC input system |
220 V AC three-phase, three-wire |
| AC power distribution |
AC input: one 3-pole 100 A circuit breaker |
| Rectifier |
Eight available slots
A maximum of eight R4850G2s |
| SSU (optional) |
N/A |
| PV distribution unit (PVDU) (optional) |
N/A |
| SMU and UIM |
SMU02B and UIM02C |
| DC power distribution |
BLVD route
Standard circuit breakers: four 1-pole 63 A circuit breakers, two 1-pole 16 A circuit breakers, and two 1-pole 10 A circuit breakers
Extended circuit breaker: eight 1-pole 1–63 A circuit breakers |
| LLVD route
Standard circuit breakers: two 1-pole 100 A circuit breakers, two 1-pole 63 A circuit breakers, four 1-pole 32 A circuit breakers, and two 1-pole 16 A circuit breakers
Extended circuit breakers: two 1-pole 1–125 A circuit breakers and eight 1-pole 1–63 A circuit breakers |
| Battery route: four 1-pole 125 A circuit breakers |
| DC-DC power system (optional) |
N/A |
| Baseband unit (BBU) components (optional) |
N/A |
| Battery |
A maximum of four 150 Ah battery strings |
| Space for customer equipment |
N/A |
| Sensors |
Mandatory: one battery temperature sensor
Optional: one temperature and humidity sensor |
| SPD |
AC surge protection. Nominal lightning strike discharge current: 20 kA (8/20 µs); maximum lightning strike discharge current: 40 kA (8/20 µs)
DC surge protection. Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs) |
| Maximum output power |
24 kW |
| Electrical Specifications |
| AC input |
Input system |
220 V AC three-phase, three-wire |
| Input voltage |
85–300 V AC |
| Input frequency |
Frequency range: 45–66 Hz; nominal frequency: 50 Hz or 60 Hz |
| PF |
≥ 0.99 (rated input, full load) |
| THD |
≤ 10% (Vin = 208 V AC, 220 V AC, 230 V AC; 50%–100% load) |
| DC output |
Output voltage range |
–42 V DC to –58 V DC |
| Default output voltage |
–53.5 V DC |
| Output power |
Maximum output power = Output power of a single rectifier x Number of rectifiers + Output power of a single SSU x Number of SSUs |
| Regulated voltage precision |
≤ ±1% |
| Ripple and noise |
≤ 200 mVp-p |
| Psophometrically weighted noise |
≤ 2 mV |
| Current imbalance |
< ±5% (50%–100% load) |
| AC input protection |
AC input overvoltage protection threshold |
> 300 V AC |
| AC input overvoltage recovery threshold |
When the voltage is restored to 290 V AC, the output resumes. |
| AC input undervoltage protection threshold |
< 85 V AC |
| AC input undervoltage recovery threshold |
When the voltage is restored to 90 V AC, the output resumes. |
| DC output protection |
DC output overvoltage protection threshold |
–58.5 V DC to –60.5 V DC
1. If overvoltage occurs due to an internal fault, the rectifier locks out.
2. If the external voltage is greater than –63 V for more than 500 ms, the rectifier locks out. |
| AC surge protection |
Nominal lightning strike discharge current: 20 kA (8/20 µs); maximum lightning strike discharge current: 40 kA (8/20 µs) |
| DC surge protection |
Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs) |
| Safety and regulatory design |
IEC/EN60950-1 |
| Mean time between failures (MTBF) |
200,000 hours |