TP48400B-N20B3 Indoor Site Power Cabinet
in stock inquire lead time
Supports a maximum of four 150 Ah battery strings
Supports a maximum of eight R4850G2s
Site monitoring unit: SMU02B, supports WebUI after installing the specific WiFi module using the USB port
User interface module: UIM02C
Wide input voltage range of 85 V AC to 300 V AC
Can be connected to solar power inputs with a wide voltage range of 58 V DC to 150 V DC.
The TP48400B-N20B3 is an indoor communications power system that converts AC power into stable DC power and supplies the DC power to -48 V DC communications equipment. It has a maximum output current of 400 A.
Cabinet Specifications |
||
Cabinet dimensions (H x W x D) | 2000 mm x 600 mm x 600 mm | |
Weight | ≤ 126 kg (excluding rectifiers and batteries) | |
Protection level | IP20 | |
Installation mode | Installed on a concrete floor or an ESD floor | |
Maintenance mode | Maintained from the front and installed on a wall with a clearance of at least 100 mm | |
Cabling | Routed in and out from the top of the cabinet | |
Configuration | ||
AC input system | 220/380 V AC three-phase, four-wire | |
AC power distribution | AC input: one 3-pole 63 A circuit breaker | |
Rectifier | Eight available slots
A maximum of eight R4850G2s |
|
SSU (optional) | N/A | |
PV distribution unit (PVDU) (optional) | N/A | |
SMU and UIM | SMU02B and UIM02C | |
DC power distribution | BLVD route
Standard circuit breakers: four 1-pole 63 A circuit breakers, two 1-pole 16 A circuit breakers, and two 1-pole 10 A circuit breakers Extended circuit breaker: eight 1-pole 1–63 A circuit breakers |
|
LLVD route
Standard circuit breakers: two 1-pole 100 A circuit breakers, two 1-pole 63 A circuit breakers, four 1-pole 32 A circuit breakers, and two 1-pole 16 A circuit breakers Extended circuit breakers: two 1-pole 1–125 A circuit breakers and eight 1-pole 1–63 A circuit breakers |
||
Battery route: four 1-pole 125 A circuit breakers | ||
DC-DC power system (optional) | N/A | |
Baseband unit (BBU) components (optional) | N/A | |
Battery | A maximum of four 150 Ah battery strings | |
Space for customer equipment | N/A | |
Sensors | Mandatory: one battery temperature sensor Optional: one temperature and humidity sensor |
|
SPD | AC surge protection. Nominal lightning strike discharge current: 20 kA (8/20 µs); maximum lightning strike discharge current: 40 kA (8/20 µs) DC surge protection. Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs) |
|
Maximum output power | 24 kW | |
Electrical Specifications | ||
AC input | Input system | 220/380 V AC three-phase, four-wire |
Input voltage | 85–300 V AC | |
Input frequency | Frequency range: 45–66 Hz; nominal frequency: 50 Hz or 60 Hz | |
PF | ≥ 0.99 (rated input, full load) | |
THD | ≤ 10% (Vin = 208 V AC, 220 V AC, 230 V AC; 50%–100% load) | |
DC output | Output voltage range | –42 V DC to –58 V DC |
Default output voltage | –53.5 V DC | |
Output power | Maximum output power = Output power of a single rectifier x Number of rectifiers + Output power of a single SSU x Number of SSUs | |
Regulated voltage precision | ≤ ±1% | |
Ripple and noise | ≤ 200 mVp-p | |
Psophometrically weighted noise | ≤ 2 mV | |
Current imbalance | < ±5% (50%–100% load) | |
AC input protection | AC input overvoltage protection threshold | > 300 V AC |
AC input overvoltage recovery threshold | When the voltage is restored to 290 V AC, the output resumes. | |
AC input undervoltage protection threshold | < 85 V AC | |
AC input undervoltage recovery threshold | When the voltage is restored to 90 V AC, the output resumes. | |
DC output protection | DC output overvoltage protection threshold | –58.5 V DC to –60.5 V DC
1. If overvoltage occurs due to an internal fault, the rectifier locks out. 2. If the external voltage is greater than –63 V for more than 500 ms, the rectifier locks out. |
AC surge protection | Nominal lightning strike discharge current: 20 kA (8/20 µs); maximum lightning strike discharge current: 40 kA (8/20 µs) | |
DC surge protection | Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs) | |
Safety and regulatory design | IEC/EN60950-1 | |
Mean time between failures (MTBF) | 200,000 hours |
As a global leading professional Huawei network hardware and solution provider, we have delivered Huawei, ZTE, Nokia, CISCO, Fiberhome, etc, equipment to 500+ customer groups in 90+ countries over the past 10 years. Know more
Strict 3-Level Quality Control procedure: 1st-Level inspection; 2nd-Level In-stock test; 3rd-Level 24-hour pre-delivery test to guarantee premium quality. Know more
What we offer to our customers is value rather than price. We enable customers to enjoy the benefit of our reliable delivery products and generate more value to the greatest extent. Know more
We provide customers with personalized and professional tech support by remote diagnosis, fault-location and troubleshooting. "We are here to help you instantly when you need it."
We continuously offer flexible payment methods such as Wire Transfer, Paypal, L/C, Western Union and Alipay, to help customer enjoy a more convenient shopping experience. Know more
We provide extensive document resources to guide our customers to targetly solve the problem they may meet. Know more
Our products come with 1-year warranty. Customers can ask for a repair, replacement or refund for a major product failure. Know more
We won't stop to develop rapid and cost effective shipping options, providing the excellent experience to our global customers. Know more
We offer not only network products but also network proposal, mainstream and cost-effective solution to assist customers eliminate the concerns.
Reviews
There are no reviews yet.