| Cabinet Specifications |
||
| Cabinet dimensions (H x W x D) | 2000 mm x 600 mm x 600 mm | |
| Weight | ≤ 126 kg (excluding rectifiers and batteries) | |
| Protection level | IP20 | |
| Installation mode | Installed on a concrete floor or an ESD floor | |
| Maintenance mode | Maintained from the front and installed on a wall with a clearance of at least 100 mm | |
| Cabling | Routed in and out from the top of the cabinet | |
| Configuration | ||
| AC input system | 220/380 V AC three-phase, four-wire | |
| AC power distribution | AC input: one 3-pole 63 A circuit breaker | |
| Rectifier | Eight available slots
A maximum of eight R4850G2s |
|
| SSU (optional) | N/A | |
| PV distribution unit (PVDU) (optional) | N/A | |
| SMU and UIM | SMU02B and UIM02C | |
| DC power distribution | BLVD route
Standard circuit breakers: four 1-pole 63 A circuit breakers, two 1-pole 16 A circuit breakers, and two 1-pole 10 A circuit breakers Extended circuit breaker: eight 1-pole 1–63 A circuit breakers |
|
| LLVD route
Standard circuit breakers: two 1-pole 100 A circuit breakers, two 1-pole 63 A circuit breakers, four 1-pole 32 A circuit breakers, and two 1-pole 16 A circuit breakers Extended circuit breakers: two 1-pole 1–125 A circuit breakers and eight 1-pole 1–63 A circuit breakers |
||
| Battery route: four 1-pole 125 A circuit breakers | ||
| DC-DC power system (optional) | N/A | |
| Baseband unit (BBU) components (optional) | N/A | |
| Battery | A maximum of four 150 Ah battery strings | |
| Space for customer equipment | N/A | |
| Sensors | Mandatory: one battery temperature sensor Optional: one temperature and humidity sensor |
|
| SPD | AC surge protection. Nominal lightning strike discharge current: 20 kA (8/20 µs); maximum lightning strike discharge current: 40 kA (8/20 µs) DC surge protection. Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs) |
|
| Maximum output power | 24 kW | |
| Electrical Specifications | ||
| AC input | Input system | 220/380 V AC three-phase, four-wire |
| Input voltage | 85–300 V AC | |
| Input frequency | Frequency range: 45–66 Hz; nominal frequency: 50 Hz or 60 Hz | |
| PF | ≥ 0.99 (rated input, full load) | |
| THD | ≤ 10% (Vin = 208 V AC, 220 V AC, 230 V AC; 50%–100% load) | |
| DC output | Output voltage range | –42 V DC to –58 V DC |
| Default output voltage | –53.5 V DC | |
| Output power | Maximum output power = Output power of a single rectifier x Number of rectifiers + Output power of a single SSU x Number of SSUs | |
| Regulated voltage precision | ≤ ±1% | |
| Ripple and noise | ≤ 200 mVp-p | |
| Psophometrically weighted noise | ≤ 2 mV | |
| Current imbalance | < ±5% (50%–100% load) | |
| AC input protection | AC input overvoltage protection threshold | > 300 V AC |
| AC input overvoltage recovery threshold | When the voltage is restored to 290 V AC, the output resumes. | |
| AC input undervoltage protection threshold | < 85 V AC | |
| AC input undervoltage recovery threshold | When the voltage is restored to 90 V AC, the output resumes. | |
| DC output protection | DC output overvoltage protection threshold | –58.5 V DC to –60.5 V DC
1. If overvoltage occurs due to an internal fault, the rectifier locks out. 2. If the external voltage is greater than –63 V for more than 500 ms, the rectifier locks out. |
| AC surge protection | Nominal lightning strike discharge current: 20 kA (8/20 µs); maximum lightning strike discharge current: 40 kA (8/20 µs) | |
| DC surge protection | Differential mode: 10 kA (8/20 µs); common mode: 20 kA (8/20 µs) | |
| Safety and regulatory design | IEC/EN60950-1 | |
| Mean time between failures (MTBF) | 200,000 hours | |