UPS2000-A, 1 kVA-3 kVA UPS
in stock inquire lead time
UPS2000-A, 1 kVA-3 kVA UPS
UPS2000-A, the tower-mounted model provides three configurations: 1 kVA, 2 kVA, and 3 kVA.
Each configuration has standard backup time or long backup time.
Mains input electrical specifications
Item | 1 kVA | 2 kVA | 3 kVA | |
Input power cable | Single-phase (L/N) input +PE cable | |||
Rated input voltage | 200 V AC/208 V AC/220 V AC/230 V AC/240 V AC | |||
Input voltage range | Lowest conversion voltage | When the ambient temperature is 0–35°C: | ||
160 V AC/140 V AC/120 V AC/110 V AC±5% (depending on the load rate: 100%–80%/80%–70%/70%–60%/60%–0) | ||||
When the ambient temperature is 35–40°C: | ||||
175 V AC/155 V AC/135 V AC/125 V AC±5% (depending on the load rate: 100%–80%/80%–70%/70%–60%/60%–0) | ||||
Lowest recovery voltage | When the ambient temperature is 0–35°C: | |||
175 V AC/155 V AC/135 V AC/125 V AC±5% (depending on the load rate: 100%–80%/80%–70%/70%–60%/60%–0) | ||||
When the ambient temperature is 35–40°C: | ||||
190 V AC/170 V AC/150 V AC/140 V AC±5% (depending on the load rate: 100%–80%/80%–70%/70%–60%/60%–0) | ||||
Highest conversion voltage | 300 V AC±5% (load rate: less than 80%) | |||
280 V AC±5% (load rate: 80%–100%; transfer to battery mode after 15 minutes) | ||||
Highest recovery voltage | 290 V AC±5% (load rate: less than 80%) | |||
270 V AC±5% (load rate: greater than 80%) | ||||
Input power factor (100% resistive load) | > 0.99 | |||
Startup voltage | 120–280 V AC | |||
Generator input capacity | Minimum 1.5 times the UPS rated capacity |
Bypass Input Electrical Specifications
Item | 1 kVA | 2 kVA | 3 kVA |
Bypass voltage tolerance | 170 V –264 V AC | ||
Bypass frequency tolerance | 47–53 Hz or 57–63 Hz | ||
Bypass overload capability | 110%–120%, 30 minutes | ||
120%–130%, 10 minutes | |||
130%–150%, 1 minute | |||
Input mode | One mains input |
Output electrical specifications
Item | 1 kVA | 2 kVA | 3 kVA | |
Rated capacity | 1000 VA/800 W | 2000 VA/1600 W | 3000 VA/2400 W | |
Output power factor (PF) | 0.8 | |||
Rated output voltage | 220 V AC/230 V AC/240 V AC | |||
Output voltage tolerance | ±1% | |||
Output frequency range | In normal mode, the UPS output frequency is consistent with the input frequency, which is 50 Hz or 60 Hz with the tolerance of ±3 Hz. | |||
In battery mode, the frequency is 50 Hz or 60 Hz (tolerance ±0.05%). | ||||
Total distortion of output voltage waveform (THDv) | < 6% (non-resistive load) | |||
< 3% (resistive load) | ||||
Crest factor | A maximum of 3:1 | |||
Inverter overload capability | When the ambient temperature is 0–35°C: | |||
105%–110%: The UPS transfers to bypass mode (from normal mode) or shuts down automatically (from battery mode) after 10 min. | ||||
110%–130%: The UPS transfers to bypass mode (from normal mode) or shuts down automatically (from battery mode) after 1 min. | ||||
130%–150%: The UPS transfers to bypass mode (from normal mode) or shuts down automatically (from battery mode) after 3s. | ||||
> 150%: The UPS transfers to bypass mode (from normal mode) or shuts down automatically (from battery mode) after no more than 0.5s. | ||||
When the ambient temperature is 35–40°C: | ||||
105%–110%: The UPS transfers to bypass mode (from normal mode) or shuts down automatically (from battery mode) after 5 min. | ||||
110%–130%: The UPS transfers to bypass mode (from normal mode) or shuts down automatically (from battery mode) after 30s. | ||||
130%–150%: The UPS transfers to bypass mode (from normal mode) or shuts down automatically (from battery mode) after 1.5s. | ||||
> 150%: The UPS transfers to bypass mode (from normal mode) or shuts down automatically (from battery mode) after no more than 0.5s. | ||||
Dynamic voltage transient | ±5% | |||
Average frequency tracking rate | 1 Hz/s | |||
Transfer time | Transferring from normal mode to battery mode | 0 | ||
Bypass to ECO or ECO to bypass | 4 ms (100% resistive load) | |||
Waveform (battery mode) | Sine wave |
Battery electrical specifications
Item | 1 kVA | 2 kVA | 3 kVA | |
Rated battery voltage | Standard backup time model | 24 V DC | 48 V DC | 72 V DC |
Long backup time model | 36 V DC | 72 V DC | 96 V DC | |
Number of batteries | Standard backup time model | 2 | 4 | 6 |
Long backup time model | 3 | 6 | 8 | |
Battery leakage current | Standard backup time model | 17 µA | 25.7 µA | 27.4 µA |
Long backup time model | 25.4 µA | 28.5 µA | 32.8 µA | |
Battery type | 12 V DC VRLA battery | |||
Battery capacity | Standard backup time model | 9 Ah | ||
Long backup time model | 18 Ah | |||
Battery EOD voltage | Standard backup time model | 1.6–1.88 V/cell | ||
Long backup time model | 1.75 V/cell | |||
Backup time | Standard backup time model | ≥ 4 minutes (at rated full load), tested before delivery | ||
Long backup time model | Depending on the capacity of external batteries | |||
Charger rated charge | Standard backup time model | 1:00 AM | ||
Long backup time model | 4:00 AM | |||
Float charging voltage | Standard backup time model | 27.3 V DC±1% | 54.7 V DC±1% | 82.1 V DC±1% |
Long backup time model | 41.0 V DC±1% | 82.1 V DC±1% | 109.4 V DC±1% | |
Equalized charging voltage | Standard backup time model | 28.3 V DC±1% | 56.6 V DC±1% | 84.9 V DC±1% |
Long backup time model | 42.5 V DC±1% | 84.9 V DC±1% | 113.3 V DC±1% |
As a global leading professional Huawei network hardware and solution provider, we have delivered Huawei, ZTE, Nokia, CISCO, Fiberhome, etc, equipment to 500+ customer groups in 90+ countries over the past 10 years. Know more
Strict 3-Level Quality Control procedure: 1st-Level inspection; 2nd-Level In-stock test; 3rd-Level 24-hour pre-delivery test to guarantee premium quality. Know more
What we offer to our customers is value rather than price. We enable customers to enjoy the benefit of our reliable delivery products and generate more value to the greatest extent. Know more
We provide customers with personalized and professional tech support by remote diagnosis, fault-location and troubleshooting. "We are here to help you instantly when you need it."
We continuously offer flexible payment methods such as Wire Transfer, Paypal, L/C, Western Union and Alipay, to help customer enjoy a more convenient shopping experience. Know more
We provide extensive document resources to guide our customers to targetly solve the problem they may meet. Know more
Our products come with 1-year warranty. Customers can ask for a repair, replacement or refund for a major product failure. Know more
We won't stop to develop rapid and cost effective shipping options, providing the excellent experience to our global customers. Know more
We offer not only network products but also network proposal, mainstream and cost-effective solution to assist customers eliminate the concerns.
Reviews
There are no reviews yet.