| Mains input electrical specifications |
| Item |
6 kVA |
10 kVA |
| Single-Phase Input |
Single-Phase Input |
Three-Phase Input |
| Power system |
1Ph (L/N) + PE |
1Ph (L/N) + PE |
3Ph (L1/L2/L3/N) + PE |
| Rated input voltage |
220 V AC/230 V AC/240 V AC |
220 V AC/230 V AC/240 V AC |
380 V AC/400 V AC/415 V AC |
| Input voltage range |
Phase voltage: 80 V AC to 280 V AC (When the ambient temperature ranges from –5°C to +40°C, the load is linearly derated from 100% to 40% when the voltage ranges from 176 V AC to 80 V AC.) |
Phase voltage: 80 V AC to 280 V AC (When the ambient temperature ranges from –5°C to +40°C, the load is linearly derated from 100% to 40% when the voltage ranges from 176 V AC to 80 V AC.) |
Line voltage: 138 V AC to 484 V AC (When the ambient temperature ranges from –5°C to +40°C, the load is linearly derated from 100% to 40% when the voltage ranges from 176 V AC to 80 V AC.) |
| Rated frequency |
50 Hz/60 Hz |
| Frequency range |
40–70 Hz |
| Input power factor |
≥ 0.99 (100% resistive load) |
| Generator input capacity |
Minimum: 1.35 times of the UPS rated capacity |
| Overvoltage category |
OVC II |
| Bypass input electrical specifications |
| Power system |
Single-phase, three-wire |
| Input voltage |
220 V AC/230 V AC/240 V AC |
| Voltage range |
Upper threshold: +10%, +15%, +20%, or +25% at 220 V AC |
| Upper threshold: +10%, +15%, or +20% at 230 V AC |
| Upper threshold: +10% or +15% at 240 V AC |
| Lower threshold: –10%, –20%, –30%, –40%, –50%, or –60% |
| Rated frequency |
50 Hz/60 Hz |
| Frequency range |
50/60±6 Hz (adjustable with a tolerance of 0.5–6 Hz, ±2 Hz by default) |
| Input system |
Supports only one power source. |
| Overvoltage category |
OVC II |
| Output electrical specifications |
| Power system |
Single-phase, three-wire |
| Rated output voltage |
220 V AC/230 V AC/240 V AC |
| Output power factor |
1 |
| Output voltage tolerance |
±1% |
| Output short-circuit current |
6K: Ipeak: 3.5 kA; Irms: 2.5 kA |
| 10K: Ipeak: 4.0 kA; Irms: 3.0 kA |
| Voltage distortion |
Linear load THD < 1% @ Input voltage THDv < 5% |
| Non-linear load THD < 3% @ Input voltage THDv < 5% |
| Inverter overload capability |
Normal mode: |
| 105% < load ≤ 125%: transfers to bypass mode after 10 min |
| 125% < load ≤ 150%: transfers to bypass mode after 60s |
| Load > 150%: transfers to bypass mode after 200 ms |
| Battery mode: |
| 100% ≤ load < 105%: loaded for a long time |
| 105% ≤ load < 125%: for 30s |
| Load ≥ 125%: for 200 ms |
|
| NOTE: |
| In battery mode, with the rated input voltage, the UPS transfers to the bypass mode if the bypass is normal and stops supplying power if the bypass is abnormal. |
|
| Bypass overload capability |
When the ambient temperature is below 40°C: |
| Load ≤ 125%: overload for extended periods |
| 125%–150% load: no output after 60s |
| Load > 150%: no output after 200 ms |
| Dynamic voltage transient |
≤ ±5% |
| Average frequency tracking rate |
0.1–2 Hz/s, 2 Hz/s for a single UPS, 1 Hz/s for a parallel system |
| Load adaptability |
Resistive load, resistive-capacitive load, inductive load (50%), rectification load, capacitive load, half-wave load, and half-wave rectification load |
| Battery electrical specifications |
| Battery voltage |
Lead-acid battery: 12 V battery, 12–20 batteries, 0 batteries by default |
| If there are 16 or more batteries, the output power is not derated. If there are fewer than 16 batteries, the output power is derated by 10% each time one battery is removed. |
| Battery cold start |
If a mains outage occurs, batteries can start the UPS to supply power to loads. |
| Charger output power |
Rated full load, maximum charge power: 1.8 kW (for 6 kVA), 3 kW (for 10 kVA) |
| Charge voltage |
Lead-acid battery: |
| Equalized charging voltage range: 2.3–2.4 V/cell; default voltage: 2.35 V/cell |
| Float charging voltage range: 2.23–2.3 V/cell; default voltage: 2.25 V/cell |
| Battery type |
VRLA (lead-acid battery) |
| Battery string sharing |
Supported |
| System electrical specifications |
| Number of parallel UPSs |
4 |
| No-load loss |
6 kVA: < 60 W |
| 10 kVA: < 90 W |
| Note: rated input, rated output, no load, no battery connected, no optional card |
| Power distribution system |
TN, TN-C, TN-CS, TT |
| Physical specifications |
| Item |
6 kVA |
10 kVA |
| Dimensions (H x W x D) |
43 mm x 442 mm x 505 mm |
86 mm x 442 mm x 505 mm |
| Weight |
11 kg |
16 kg |
| IP rating |
IP20 |
| Operating temperature |
–5°C to +50°C |
| Temperature derating coefficient: –5°C ≤ T ≤ +40°C: not derated; 41°C < T ≤ 45°C: derated to 0.9 times of rated output power; 46°C < T ≤ 50°C: derated to 0.8 times of rated output power |
| Relative humidity |
0%–95% RH (non-condensing) |
| Altitude |
0–4000 m |
| When the altitude is greater than 1000 m, the power is derated as described in IEC 62040-3. The highest operating altitude is 4000 m. |
| Storage and transportation temperature |
–40ºC to +70ºC |