Item
|
400 kVA
|
500 kVA
|
|
|
Cabling
|
Routed in and out from the top or bottom
|
|
IP rating
|
IP20 (IP21 can be reached by configuring an IP21 component.)
|
|
Dimensions (H x W x D)
|
2000 mm x 1200 mm x 850 mm
|
2000 mm x 1400 mm x 850 mm
|
|
Communication
|
Supports dry contacts, RS485 ports, and FE ports. Supports the Simple Network Management Protocol (SNMP).
|
|
Weight
|
676 kg
|
746 kg
|
1030 kg
|
Internal switch specifications
|
UPS
|
Maintenance Bypass Switch
|
Mains Input Switch
|
Bypass Input Switch
|
Output Switch
|
|
UPS5000-A-400K-FTS
|
1000 V AC/630 A/3P
|
1000 V AC/800 A/3P
|
1000 V AC/630 A/3P
|
1000 V AC/630 A/3P
|
|
UPS5000-A-500K-FTS
|
1000 V AC/800 A/3P
|
1000 V AC/1000 A/3P
|
1000 V AC/800 A/3P
|
1000 V AC/800 A/3P
|
|
UPS5000-A-600K-FTS
|
1000 V AC/1000 A/3P
|
1000 V AC/1250 A/3P
|
1000 V AC/1000 A/3P
|
1000 V AC/1000 A/3P
|
Environmental specifications
|
Item
|
Specifications
|
|
Operating temperature
|
0°C to 40°C
|
|
Storage temperature
|
–40°C to +70°C
|
|
Relative humidity
|
0–95% RH (non-condensing)
|
|
Altitude
|
0–1000 m
When the altitude is higher than 1000 m, the power is derated as described in IEC 62040-3. The upper limit of the altitude is 4000 m.
|
Safety regulations and EMC
|
Item
|
Specifications
|
|
Safety regulations
|
CE
|
EN 62040-1:2013
|
|
CB
|
IEC 62040-1:2013
|
|
TUV
|
EN 62040-1:2013
|
|
TLC
|
YD/T 1095-2018
|
|
EMC
|
Conducted emission
|
EN/IEC 62040-2, C3
|
|
Radiated emission
|
EN/IEC 62040-2, C3
|
|
Low-frequency signal interference
|
IEC 61000-2-2
|
|
ESD immunity
|
IEC 61000-4-2
|
|
Conducted susceptibility
|
EN 61000-4-6
EN/IEC 62040-2
IEC 61000-4-6
|
|
Radiated susceptibility
|
EN 61000-4-3
EN/IEC 62040-2
IEC 61000-4-3
|
|
Electrical fast transient
|
EN/IEC 62040-2
IEC 61000-4-4
|
|
Surge
|
EN/IEC 62040-2
IEC 61000-4-5
|
|
Power magnetic susceptibility
|
IEC 61000-4-8
|
|
Voltage dip and temporary interruption
|
IEC 61000-4-11
|
Mains input electrical specifications
|
Item
|
Specifications
|
|
Input system
|
Three-phase, four-wire, and PE
|
|
Rated input voltage
|
380 V AC/400 V AC/415 V AC (line voltage)
|
|
Input voltage range
|
- 80–280 V AC (phase voltage)
- 30°C < Ambient temperature ≤ 40°C: The UPS supports full load when the voltage range is 198–280 V AC. The load is derated to 35% when the voltage range is 80–198 V AC.
- 0°C ≤ Ambient temperature ≤ 30°C: The UPS supports full load when the voltage range is 187–280 V AC. The load is derated to 35% when the voltage range is 80–187 V AC.
|
|
Rated frequency
|
50/60 Hz
|
|
Input frequency range
|
40–70 Hz
|
|
Input power factor
|
- > 0.99 (full load)
- > 0.98 (half load)
|
|
THDi
|
- THDi < 3% (full linear load)
- THDi < 5% (full non-linear load)
|
Bypass input specifications
|
Item
|
Specifications
|
|
Input system
|
Three-phase, four-wire, and PE
|
|
Rated input voltage
|
380 V AC/400 V AC/415 V AC (line voltage)
|
|
Rated frequency
|
50/60 Hz
|
|
Input frequency range
|
±6 Hz (adjustable, 0.5–6 Hz, ±2 Hz by default)
|
|
Input mode
|
The mains input and bypass input share a power source or use different power sources.
|
Battery electrical specifications
|
Item
|
Specifications
|
|
Number of batteries
|
12 V batteries (30–44 batteries optional, 40 by default). If there are 40 to 44 batteries, the output power is not derated. If there are 38 or 36 batteries, the output power is derated to 0.9. If there are 34 or 32 batteries, the output power is derated to 0.8. If there are 30 batteries, the output power is derated to 0.75.
|
|
Battery management
|
Intelligent battery management
|
|
Cold start
|
If a mains outage occurs, batteries can start the UPS to supply power to loads.
|
|
Battery string sharing
|
Battery string sharing is supported in a parallel system. No battery string is shared by default.
|
|
Charge voltage
|
- Equalized charge voltage: 2.3–2.4 V/cell, default: 2.35 V/cell (30–42 batteries)
- Equalized charge voltage: 2.3–2.35 V/cell, default: 2.35 V/cell (44 batteries)
- Float charge voltage: 2.23–2.3 V/cell, default: 2.25 V/cell (30–44 batteries)
|
Output electrical specifications
|
Item
|
Specifications
|
|
Output system
|
Three-phase four-wire, and PE
|
|
Voltage
|
380 V AC/400 V AC/415 V AC±1% (line voltage)
|
|
THDv
|
- THDv ≤ 1% (100% linear load)
- THDv ≤ 4% (100% non-linear load)
|
|
Output power factor
|
0.9
|
|
Transfer time
|
|
|
Phase difference (three phases)
|
120 degrees (tolerance: ±2 degrees)
|
|
100% unbalanced load voltage imbalance
|
±3%
|
|
Overload capability
|
Inverter overload capability:
- 105% < Linear load ≤ 110%: transfers to bypass mode after 60 minutes
-
0°C ≤ Ambient temperature ≤ 30°C, 110% < Linear load ≤ 125%: transfers to bypass mode after 10 minutes
30°C < Ambient temperature ≤ 40°C, 110% < Linear load ≤ 125%: transfers to bypass mode after 3 minutes
- 125% < Linear load ≤ 150%: transfers to bypass mode after 30s
- Linear load > 150% or a short circuit occurs: runs for 200 ms
|
System electrical specifications
|
Item
|
Specifications
|
|
Voltage display precision
|
Input voltage, bypass voltage, output voltage, bus voltage, and charge voltage: 1%
|
|
Frequency display precision
|
Input, bypass, and output frequency: 1%
|
|
ECO in a parallel system
|
Supported
|