UPS5000-A-400 kVA
in stock inquire lead time
UPS5000-A-400 kVA
Uses a modular design, which facilitates maintenance and capacity expansion.
Adopts intelligent control.
Power module consists of a rectifier, inverter, and DC/DC converter.
Converts inputs into pure high-quality sine wave outputs by using the high-frequency switching technology.
Physical specifications
Item |
400 kVA |
500 kVA |
|
Cabling |
Routed in and out from the top or bottom |
||
IP rating |
IP20 (IP21 can be reached by configuring an IP21 component.) |
||
Dimensions (H x W x D) |
2000 mm x 1200 mm x 850 mm |
2000 mm x 1400 mm x 850 mm |
|
Communication |
Supports dry contacts, RS485 ports, and FE ports. Supports the Simple Network Management Protocol (SNMP). |
||
Weight |
676 kg |
746 kg |
1030 kg |
Internal switch specifications
UPS |
Maintenance Bypass Switch |
Mains Input Switch |
Bypass Input Switch |
Output Switch |
UPS5000-A-400K-FTS |
1000 V AC/630 A/3P |
1000 V AC/800 A/3P |
1000 V AC/630 A/3P |
1000 V AC/630 A/3P |
UPS5000-A-500K-FTS |
1000 V AC/800 A/3P |
1000 V AC/1000 A/3P |
1000 V AC/800 A/3P |
1000 V AC/800 A/3P |
UPS5000-A-600K-FTS |
1000 V AC/1000 A/3P |
1000 V AC/1250 A/3P |
1000 V AC/1000 A/3P |
1000 V AC/1000 A/3P |
Environmental specifications
Item |
Specifications |
|||
Operating temperature |
0°C to 40°C |
|||
Storage temperature |
–40°C to +70°C |
|||
Relative humidity |
0–95% RH (non-condensing) |
|||
Altitude |
0–1000 m When the altitude is higher than 1000 m, the power is derated as described in IEC 62040-3. The upper limit of the altitude is 4000 m. |
Safety regulations and EMC
Item |
Specifications |
|
Safety regulations |
CE |
EN 62040-1:2013 |
CB |
IEC 62040-1:2013 |
|
TUV |
EN 62040-1:2013 |
|
TLC |
YD/T 1095-2018 |
|
EMC |
Conducted emission |
EN/IEC 62040-2, C3 |
Radiated emission |
EN/IEC 62040-2, C3 |
|
Low-frequency signal interference |
IEC 61000-2-2 |
|
ESD immunity |
IEC 61000-4-2 |
|
Conducted susceptibility |
EN 61000-4-6 EN/IEC 62040-2 IEC 61000-4-6 |
|
Radiated susceptibility |
EN 61000-4-3 EN/IEC 62040-2 IEC 61000-4-3 |
|
Electrical fast transient |
EN/IEC 62040-2 IEC 61000-4-4 |
|
Surge |
EN/IEC 62040-2 IEC 61000-4-5 |
|
Power magnetic susceptibility |
IEC 61000-4-8 |
|
Voltage dip and temporary interruption |
IEC 61000-4-11 |
Mains input electrical specifications
Item |
Specifications |
|||
Input system |
Three-phase, four-wire, and PE |
|||
Rated input voltage |
380 V AC/400 V AC/415 V AC (line voltage) |
|||
Input voltage range |
|
|||
Rated frequency |
50/60 Hz |
|||
Input frequency range |
40–70 Hz |
|||
Input power factor |
|
|||
THDi |
|
Bypass input specifications
Item |
Specifications |
|||
Input system |
Three-phase, four-wire, and PE |
|||
Rated input voltage |
380 V AC/400 V AC/415 V AC (line voltage) |
|||
Rated frequency |
50/60 Hz |
|||
Input frequency range |
±6 Hz (adjustable, 0.5–6 Hz, ±2 Hz by default) |
|||
Input mode |
The mains input and bypass input share a power source or use different power sources. |
Battery electrical specifications
Item |
Specifications |
|||
Number of batteries |
12 V batteries (30–44 batteries optional, 40 by default). If there are 40 to 44 batteries, the output power is not derated. If there are 38 or 36 batteries, the output power is derated to 0.9. If there are 34 or 32 batteries, the output power is derated to 0.8. If there are 30 batteries, the output power is derated to 0.75. |
|||
Battery management |
Intelligent battery management |
|||
Cold start |
If a mains outage occurs, batteries can start the UPS to supply power to loads. |
|||
Battery string sharing |
Battery string sharing is supported in a parallel system. No battery string is shared by default. |
|||
Charge voltage |
|
Output electrical specifications
Item |
Specifications |
|||
Output system |
Three-phase four-wire, and PE |
|||
Voltage |
380 V AC/400 V AC/415 V AC±1% (line voltage) |
|||
THDv |
|
|||
Output power factor |
0.9 |
|||
Transfer time |
|
|||
Phase difference (three phases) |
120 degrees (tolerance: ±2 degrees) |
|||
100% unbalanced load voltage imbalance |
±3% |
|||
Overload capability |
Inverter overload capability:
|
System electrical specifications
Item |
Specifications |
|||
Voltage display precision |
Input voltage, bypass voltage, output voltage, bus voltage, and charge voltage: 1% |
|||
Frequency display precision |
Input, bypass, and output frequency: 1% |
|||
ECO in a parallel system |
Supported |
As a global leading professional Huawei network hardware and solution provider, we have delivered Huawei, ZTE, Nokia, CISCO, Fiberhome, etc, equipment to 500+ customer groups in 90+ countries over the past 10 years. Know more
Strict 3-Level Quality Control procedure: 1st-Level inspection; 2nd-Level In-stock test; 3rd-Level 24-hour pre-delivery test to guarantee premium quality. Know more
What we offer to our customers is value rather than price. We enable customers to enjoy the benefit of our reliable delivery products and generate more value to the greatest extent. Know more
We provide customers with personalized and professional tech support by remote diagnosis, fault-location and troubleshooting. "We are here to help you instantly when you need it."
We continuously offer flexible payment methods such as Wire Transfer, Paypal, L/C, Western Union and Alipay, to help customer enjoy a more convenient shopping experience. Know more
We provide extensive document resources to guide our customers to targetly solve the problem they may meet. Know more
Our products come with 1-year warranty. Customers can ask for a repair, replacement or refund for a major product failure. Know more
We won't stop to develop rapid and cost effective shipping options, providing the excellent experience to our global customers. Know more
We offer not only network products but also network proposal, mainstream and cost-effective solution to assist customers eliminate the concerns.
Reviews
There are no reviews yet.