UPS5000-H-800 kVA-NTN

UPS5000-H-800 kVA-NTN

in stock      inquire lead time

16 People watching this product now!
Category:

Description

UPS5000-H-800 kVA-NTN

The UPS5000 is suitable for power systems in various scenarios, including large-scale data centers or communications centers, equipment rooms of large-scale enterprises or financial systems, industrial automated equipment, and scheduling centers.

The UPS uses a modular design. It uses multiple power modules connected in parallel to deliver a high loading capacity.

The UPS5000 consists of a rectifier, inverter, and DC/DC converter.

It converts inputs into pure high-quality sine wave outputs by using the high-frequency switching technology.

 

Tech Specs

Physical Specifications

Item Specifications
Cabling mode Routed in and out from the top
Routed in and out from the bottom (if a bottom cabling cabinet is configured)
IP rating IP20
Communication Supports dry contacts, RS485 ports, and FE ports. Supports SNMP and Modbus.
Dimensions (H x W x D) 2000 mm x 1600 mm x 1000 mm
Weight < 1850 kg

Mains Input Electrical Specifications

Item Specifications
Rated voltage (line voltage) 480 V AC
Rated current (capacity: 800 kVA) 1177 A
Power system Three-phase three-wire + PE
Voltage range 0–40°C: not derated at 384–528 V, derated from 100% load to 50% load at 384–240 V, and derated from 50% load to 40% load at 240–192 V
Rated frequency 50 Hz/60 Hz
Frequency range 40–70 Hz
Power factor > 0.99 (100% load)
> 0.98 (50% load)
> 0.94 (30% load)
Harmonic current THDi < 9% (30% linear load), THDi < 6% (50% linear load), THDi < 3% (100% linear load)
THDi < 11% (30% non-linear load), THDi < 8% (50% non-linear load), THDi < 5% (100% non-linear load)
The preceding specifications can be met only when the following conditions are met:
One power source
Input THDv < 2%

Bypass Input Electrical Specifications

Item Specifications
Rated voltage (line voltage) 480 V AC
Rated current (capacity: 800 kVA) 963 A
Power system Three-phase three-wire + PE
Rated frequency 50/60 Hz
Frequency range 50/60 Hz±6 Hz (adjustable with a tolerance of 0.5–6 Hz, ±2 Hz by default)
Input mode The mains input and bypass input share a power source (by default) or use different power sources.

Battery Electrical Specifications

Item

Specifications

Battery type

  • Lead-acid battery (VRLA)
  • SmartLi: For the supported version, contact technical support.

Battery voltage (lead-acid battery)

360–600 V DC

  • 12 V batteries (30–50 batteries, 0 by default)
    • 40–50 batteries: not derated
    • 38–39 batteries: derated to 90%
    • 34–37 batteries: derated to 80%
    • 30–33 batteries: derated to 70%
  • 2 V batteries (180–300 batteries, 0 by default)
    • 240–300 batteries: not derated
    • 228–239 batteries: derated to 90%
    • 204–227 batteries: derated to 80%
    • 180–203 batteries: derated to 70%

NOTE:

  • The number of batteries is 0 by default and needs to be set based on site requirements. Batteries have no neutral wire, and an odd number of batteries are supported.
  • When the UPS works in normal mode, if the actual load rate exceeds the threshold that could trigger battery derating, an output overload alarm is generated.

Nominal discharge current (lead-acid battery)

1773 A (480 V, forty 12 V batteries in standard configuration)

Maximum discharge current (lead-acid battery)

2123 A. It is the EOD current of forty 12 V batteries in standard configuration, that is, two hundred and forty 2 V battery cells (1.67 V/cell).

Battery cold start

If a utility power outage occurs, batteries can start the UPS to supply power to loads.

Charger output power

The maximum charge power is 15% of power of a single module, and the charge current is limited to 30 A.

Battery string sharing

  • Lead-acid battery: Battery string sharing is supported in a parallel system. No battery is shared by default.
  • SmartLi 3.0: Battery string sharing is not supported.

Charging voltage (lead-acid battery)

  • Equalized charging voltage: 2.35 V/cell
  • Float charging voltage: 2.25 V/cell

Output Electrical Specifications

Item Specifications
Rated voltage 480 V AC
Current (capacity: 800 kVA) 963 A
Power system Three-phase three-wire + PE
Frequency In normal mode, the frequency is synchronous with the bypass input frequency.
In battery mode, the frequency is 50/60 Hz with a tolerance of ±0.05%.
Voltage distortion Linear load THDv < 1% (50–100% load balancing)
Non-linear load THDv < 3% (50–100% load balancing)
Power factor 1
Transfer time Double conversion mode: uninterrupted transfer 0 ms; interrupted transfer ≤ 5 ms
Output voltage imbalance Voltage imbalance: ±1%
Phase imbalance: 120±1° (balanced load and unbalanced load)
Inverter overload capability Inverter overload capability for front-to-back airflow:
100%< load ≤ 105%: long-term running (ambient temperature ≤ 30°C)
100% < load ≤ 105%: transfers to bypass mode after 60 min or longer (ambient temperature > 30°C)
105% < load ≤ 110%: transfers to bypass mode after 60 min or longer
110% < load ≤ 125%: transfers to bypass mode after 10 min or longer
125% < load ≤ 150%: transfers to bypass mode after 1 min or longer
Load > 150%: The inverter can run for 200 ms or longer.
Inverter overload capability for top airflow:
100% < load ≤ 110%: transfers to bypass mode after 60 min or longer
110% < load ≤ 125%: transfers to bypass mode after 10 min or longer (ambient temperature ≤ 30°C)
110% < load ≤ 125%: transfers to bypass mode after 1 min or longer (ambient temperature > 30°C)
125% < load ≤ 150%: transfers to bypass mode after 1 min or longer (ambient temperature ≤ 30°C)
125% < load ≤ 150%: transfers to bypass mode after 20 seconds or longer (ambient temperature > 30°C)
Load > 150%: transfers to bypass mode after 200 ms or longer
Inverter output short-circuit capability If the initial load rate is less than 40%, twice the rated current can be tolerated for 300 ms (that is, the RMS short-circuit current is 1926 A) in the case of inverter output short-circuit.
Bypass overload capability At 30°C: runs continuously at 135% load; generates only alarms and depends on overtemperature protection at 135–150% load.
At 40°C: runs continuously at 125% load; generates only alarms and depends on overtemperature protection at 125–150% load.
If the load of the bypass single-phase or three-phase is 150%–200%, the bypass will be shut down in 5 min, and the hardware depends on overtemperature protection. If the load of the bypass single-phase or three-phase is greater than 200%, the bypass will be shut down in 1 min, and the hardware depends on overtemperature protection.
Load > 1000%: runs for 100 ms

System Electrical Specifications

Item Specifications
Parallel system reliability Redundancy design for parallel signals
ECO in a parallel system Supported
No-load loss 5.5 kW
Number of parallel UPSs A maximum of four UPSs can be connected in parallel.
Power distribution system TN-S, TN-C-S, TT
NOTE:
The three-phase three-wire corner-grounded delta power system is not supported.

 

 

 

 

 

Reviews (0)

Reviews

There are no reviews yet.

Be the first to review “UPS5000-H-800 kVA-NTN”

Your email address will not be published. Required fields are marked *

You have to be logged in to be able to add photos to your review.

Why Thunder-link.com

10 Years Experience

As a global leading professional Huawei network hardware and solution provider, we have delivered Huawei, ZTE, Nokia, CISCO, Fiberhome, etc, equipment to 500+ customer groups in 90+ countries over the past 10 years. Know more

Premium Quality Guaranteed

Strict 3-Level Quality Control procedure: 1st-Level inspection; 2nd-Level In-stock test; 3rd-Level 24-hour pre-delivery test to guarantee premium quality. Know more

Value over price

What we offer to our customers is value rather than price. We enable customers to enjoy the benefit of our reliable delivery products and generate more value to the greatest extent. Know more

Tailored Technical Support

We provide customers with personalized and professional tech support by remote diagnosis, fault-location and troubleshooting. "We are here to help you instantly when you need it."

Flexible Payment

We continuously offer flexible payment methods such as Wire Transfer, Paypal, L/C, Western Union and Alipay, to help customer enjoy a more convenient shopping experience. Know more

Document Resource

We provide extensive document resources to guide our customers to targetly solve the problem they may meet. Know more

1-Year Warranty Guaranteed

Our products come with 1-year warranty. Customers can ask for a repair, replacement or refund for a major product failure. Know more

Fast Global Shipping

We won't stop to develop rapid and cost effective shipping options, providing the excellent experience to our global customers. Know more

One-Stop Solution

We offer not only network products but also network proposal, mainstream and cost-effective solution to assist customers eliminate the concerns.