Technical specifications
|
Item
|
Specifications
|
|
Cabling mode
|
Battery cables are routed in and out from the top, and input and output are connected using busbars.
|
|
Protection level
|
IP20
|
|
Communication
|
Supports dry contacts, RS485 ports, and FE ports. Supports Simple Network Management Protocol (SNMP).
|
|
Dimensions (H x W x D)
|
2200 mm x 2800 mm x 1000 mm (without a maintenance bypass unit and fan unit)
2200 mm x 3400 mm x 1000 mm (with a maintenance bypass unit)
2200 mm x 3600 mm x 1000 mm (with a fan unit)
|
|
Weight
|
2360 kg (without a maintenance bypass unit and fan unit)
2590 kg (with a maintenance bypass unit)
2660 kg (with a fan unit)
|
Environmental specifications
|
Item
|
Specifications
|
|
Operating temperature
|
0°C to 40°C
|
|
Storage temperature
|
–40°C to +70°C
|
|
Relative humidity
|
0%–95% RH (non-condensing)
|
|
Altitude
|
0–1000 m
The power is derated as described in IEC62040-3 when the altitude is from 1000 m to 4000 m. The upper limit of the altitude is 4000 m.
|
Mains input electrical specifications
|
Item
|
Specifications
|
|
System
|
Three-phase, four-wire, and PE
|
|
Rated voltage
|
380 V AC/400 V AC/415 V AC (line voltage)
|
|
Voltage range
|
80–280 V AC (phase voltage)
At 0–40°C: not derated when the voltage is 187–280 V AC; derated to 35% load when the voltage is 187–80 V AC.
|
|
Rated frequency
|
50/60 Hz
|
|
Frequency range
|
40–70 Hz
|
|
Power factor
|
- > 0.99 (full load)
- > 0.98 (half load)
|
|
Harmonic current
|
- THDi ≤ 3% (full linear load)
- THDi ≤ 5% (full non-linear load)
|
Bypass input electrical specifications
|
Item
|
Specifications
|
|
System
|
Three-phase, four-wire, and PE
|
|
Rated voltage
|
380 V AC/400 V AC/415 V AC (line voltage)
|
|
Rated frequency
|
50/60 Hz
|
|
Frequency range
|
50/60 Hz ±6 Hz (adjustable with the tolerance of 0.5–6 Hz, ±2 Hz by default)
|
|
Input mode
|
The mains input and bypass input share a power source or use different power sources.
|
Battery electrical specifications
|
Item
|
Specifications
|
|
Battery voltage (VRLA battery)
|
360 V DC to 600 V DC
12 V batteries, 30–50 batteries, 40 batteries by default
-
If there are 40 to 50 batteries, the output power is not derated.
-
If there are 36 to 39 batteries, the output power is derated to 90%.
-
If there are 32 to 35 batteries, the output power is derated to 80%.
-
If there are 30 to 31 batteries, the output power is derated to 70%.
2 V batteries, 180–300 batteries, 240 batteries by default
-
If there are 240 to 300 batteries, the output power is not derated.
-
If there are 239 to 216 batteries, the output power is derated to 90%.
-
If there are 215 to 192 batteries, the output power is derated to 80%.
-
If there are 191 to 180 batteries, the output power is derated to 70%.
|
|
Battery management
|
Intelligent battery management
|
|
Cold start by pressing one button
|
If a mains outage occurs, batteries can start the UPS to supply power to loads.
|
|
Charger output power
|
Under rated conditions, the maximum charge power of a module is 15 kW.
|
|
Charger current limit
|
Maximum 32 A for a module
|
|
Battery string sharing (VRLA battery)
|
Battery strings can be shared when power units are connected in parallel. No battery is shared by default.
|
|
Charging voltage (VRLA battery)
|
- Equalized charging voltage: 2.3–2.4 V/cell. The default voltage is 2.35 V/cell.
- Float charging voltage: 2.23–2.3 V/cell. The default voltage is 2.25 V/cell.
|
|
Minimum cell voltage (VRLA battery)
|
1.6–1.9 V/cell
|
Output electrical specifications
|
Item
|
Specifications
|
|
System
|
Three-phase, four-wire, and PE
|
|
Voltage
|
380 V AC/400 V AC/415 V AC (line voltage)
|
|
Frequency
|
- In normal mode, the frequency is synchronous with the bypass input frequency.
- In battery mode, the frequency is 50/60 Hz with a tolerance of ±0.05%.
|
|
THDv
|
- THDv ≤ 1% (full linear load)
- THDv ≤ 4% (full non-linear load)
|
|
Power factor
|
1
|
|
Transfer time
|
|
|
Output voltage imbalance
|
Voltage imbalance: ±3%; phase imbalance: ±2°
|
|
Overload capability
|
Inverter overload capability:
- 100% < load ≤ 110%, at 40°C: transfer to bypass mode after 60 minutes
- 110% < load ≤ 125%, at 0–30°C: transfer to bypass mode after 10 minutes; at 30–40°C: transfer to bypass mode after 3 minutes
- 125% < load ≤ 150%, at 25°C: transfer to bypass mode after 1 minute; at 40°C: transfer to bypass mode after 30s
- Load > 150% or a short circuit occurs: transfer to bypass mode after 200 ms
Bypass overload capability:
- The UPS runs continuously at 135% load at 30°C; generates only alarms and uses overtemperature protection at 135–150% load.
- The UPS runs continuously at 125% load at 40°C; generates only alarms and uses overtemperature protection at 125–150% load.
- The UPS runs for 5 minutes at bypass single-phase or three-phase load 150%–200% at 40°C; runs for 1 minute at bypass single-phase or three-phase load greater than 200% at 40°C.
- The UPS runs for 100 ms when the load is greater than 1000%.
|
System electrical specifications
|
Item
|
Specifications
|
|
Parallel reliability of power units
|
Redundant parallel signals
|
|
Parallel ECO function of power units
|
Supported
|
|
Number of parallel UPSs
|
2
|